Description
INTRODUCTION:
Polyvinyl chloride compound (PVC) with its inherit characterstic of toughness and flexibility over a wide temperature range is used in the manufacture of cables. PVC cables are largely used for industrial type application. They are simple to terminate & joint, handle and have significant record of trouble-free service.
All the cables design described comply to BS 6346: "PVC insulated cable for electricity Supply" which specifies requirement for cable for operation at voltages upto and including 3300 volts. It includes armoured as well as unarmoured cables.
CABLE CONSTRUCTION:
Cables are manufactured to British Standard Specification (BSS) 6346: However cables can be manufactured to all other international standards and to any special specification and customer requirements.
CONDUCTORS: STRANDED COPPER:
These are high conductivity conductors which meet the requirements of BS 6360: "Copper Conductors in insulated cables and cords (metric units) " . Where possible conductors are shapedcompacted to reduce overall cable dimensions and give a smooth profile, While compacting number and size of wire are changed, therefore conductor sizes should be designated by nominal cross sectional area rather than by stranding configuration.
STRANDED ALUMINIUM:
These are high purity Aluminium and except for single core and the smallest size the conductors are shaped to produce the most compact design. The material properties and resistance are given in BS 6791: Aluminium Conductors in insulated cables (metric unit)".
INSULATION:
This consists of extruded, PVC conforming to BS 6746: "PVC Insulation and sheath of Electric Cables" |
CORE IDENTIFICATION:
Core identification is by colour as follows:
|
NUMBER OF CORE: |
CORE COLOURS: |
Single |
Red or Black |
Two |
Red, Black |
Three |
Red, Yellow, Blue |
Four |
Red, Yellow, Blue, Black |
Black denotes the neutral and colours are phase conductors.
|
Fillers/binder tape:
Polyproplyne fillers are included between laid up cores to give smooth profile and polyproplane
tape as a binder is used over laid up cores.
BEDDING:
The bedding consists of an extruded layer of PVC compound complying with BS 6746:
ARMOUR:
With all armoured cables the direction of lay of the armour is left hand and the size of the armour is as specified. For multi core cables the armour is a single layer of galvanised steel wires_ Single core cables for use on a.c. Circuits are armoured with non magnetic material eg, aluminium.
FINISH AND FINAL PROTECTIVE COVERING
The final protective covering for all cables consists of an extruded, black (unless specified) PVC oversheath which conforms to BS 6346: for thickness and to BS 6746: for properties.
The external surface is embossed with the voltage designation.
ELECTRICAL TESTING:
At the insulation stage all cores are spark tested according to conductor size & cable voltage. Finished cables have to pass a.c. Voltage withstand test.
PACKING
Cables are packed on wooden drums of suitable size to meet minimum bending radius criteria. Drums are duly lagged to protect cable being damaged during transportation. For convenience at the installation sites drums are marked with the "Direction of Rotation" instruction. To prevent ingress of moisture both ends of cable are capped and the ends are marked red and green. At red mark the sequence of cores is clock wise i.e. Red, Yellow, Blue & Black. At green mark the sequence of cores is counter clock wise i.e. Black, Yellow, Red.
|
600/1 OOOV - SINGLE CORE
STRANDED COPPER CONDUCTOR PVC INSULATED
PVC SHEATHED CABLES.
(Cu/PVC/PVC)
|
|
NOMINAL AREA
OF CONDUCTOR |
THICKNESS
OF
INSULATION |
THICKNESS OF
OUTER SHEATH |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE WEIGHT |
Sq mm |
mm |
mm |
mm |
Kg/10.0mm |
1.0* |
1.5* |
1.5 |
2.5* |
2.5 |
4 |
6 |
10 |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
|
0.6 |
0.6 |
0.6 |
0.7 |
0.7 |
0.8 |
0.8 |
1.0 |
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
2.8 |
2.8 |
2.8 |
3.0 |
|
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.9 |
1.4 |
1.4 |
1.4 |
1.4 |
1.4 |
1.4 |
1.5 |
1.5 |
1.6 |
1.7 |
1.8 |
1.9 |
2.0 |
2.1 |
2.2 |
2.3 |
2.5 |
|
4.0 |
4.5 |
4.5 |
5.0 |
5.0 |
6.3 |
6.8 |
8.1 |
11.1 |
12.9 |
14.0 |
15.1 |
16.9 |
19.4 |
21.0 |
23.2 |
25.8 |
29.0 |
32.1 |
35.8 |
39.6 |
43.8 |
48.3 |
53.7 |
|
5.5 |
6.2 |
6.4 |
7.5 |
7.7 |
10.5 |
13.0 |
17.5 |
24.0 |
34.5 |
45.0 |
60.0 |
81.0 |
110.0 |
135.0 |
165.0 |
206.0 |
267.0 |
332.0 |
419.0 |
523.0 |
663.0 |
833.0 |
1044.0 |
|
|
*SOLID CONDUCTORS
CABLE CONFORMS TO BS 6346: & IEC 502
|
600/1000V SINGLE CORE
STRANDED COPPER CONDUCTOR PVC INSULATED ALUMINUM WIRE ARMOURED
PVC SHEATHED CABLES
(Cu/PVC/AWAlPVC)
|
NOMINAL
AREA OF CONDUCTOR |
THICKNESS
OF
INSULATION |
THICKNESS
OF
EXTRUDED BEDDING |
ARMOUR
WIRE
DIAMETER |
THICKNESS
OF
OVERSHEATH |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE WEIGHT |
Sq mm |
mm |
mm |
mm |
mm |
mm |
Kg/100m |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
|
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
2.8 |
2.8 |
2.8 |
3.0 |
|
0.8 |
0.8 |
0.8 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
1.2 |
1.2 |
1.2 |
1.4 |
1.4 |
|
1.25 |
1.25 |
1.25 |
1.6 |
1.6 |
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.0 |
2.5 |
2.5 |
|
1.5 |
1.6 |
1.6 |
1.7 |
1.7 |
1.8 |
1.9 |
1.9 |
2.1 |
2.1 |
2.2 |
2.4 |
2.5 |
|
19.1 |
21.1 |
23.4 |
26.3 |
28.3 |
30.8 |
34.1 |
37.0 |
42.0 |
45.6 |
49.7 |
55.8 |
61.0 |
|
78 |
103 |
133 |
168 |
200 |
243 |
309 |
377 |
483 |
592 |
742 |
950 |
1176 |
|
|
CABLE CONFORMS TO BS 6346
|
600/1 OOOV - SINGLE CORE
STRANDED ALUMINIUM CONDUCTOR
PVC INSULATED PVC SHEATHED CABLES
(AL/PVC/PVC)
|
NOMINAL AREA
OF CONDUCTOR |
THICKNESS OF
INSULATION |
THICKNESS OF
OVERSHEATH |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
Sq mm |
mm |
mm |
mm |
Kg/100m |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
|
1.4 |
1.4 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
2.8 |
2.8 |
2.8 |
2.8 |
3.0 |
|
1.4 |
1.4 |
1.5 |
1.5 |
1.6 |
1.7 |
1.8 |
1.9 |
2.0 |
2.1 |
2.2 |
2.3 |
2.5 |
|
15.1 |
16.9 |
19.4 |
21.0 |
23.2 |
25.8 |
29.0 |
32.1 |
35.8 |
39.6 |
43.8 |
48.3 |
53.7 |
|
28 |
36 |
48 |
57 |
69 |
86 |
109 |
134 |
167 |
206 |
244 |
294 |
375 |
|
|
600/1 OOOV - SINGLE CORE
STRANDED ALUMINIUM CONDUCTOR PVC INSULATED
ALUMINIUM WIRE ARMOURED
PVC SHEATHED CABLES
(AL/PVC/ AWA/PVC)
|
NOMINAL
AREA OF CONDUCTOR |
THICKNESS
OF
INSULATION |
THICKNESS
OF
EXTRUDED BEDDING |
ARMOUR
WIRE
DIAMETER |
THICKNESS
OF
OVERSHEATH |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE WEIGHT |
Sq mm |
mm |
mm |
mm |
mm |
mm |
Kg/100m |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
|
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
2.8 |
2.8 |
2.8 |
3.0 |
|
0.8 |
0.8 |
0.8 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
1.2 |
1.2 |
1.2 |
1.4 |
1.4 |
|
1.25 |
1.25 |
1.25 |
1.6 |
1.6 |
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.0 |
2.5 |
2.5 |
|
1.5 |
1.6 |
1.6 |
1.7 |
1.7 |
1.8 |
1.9 |
1.9 |
2.1 |
2.1 |
2.2 |
2.4 |
2.5 |
|
19.1 |
21.1 |
23.4 |
26.3 |
28.3 |
30.8 |
34.1 |
37.0 |
42.0 |
45.6 |
49.7 |
55.8 |
61 |
|
66 |
79 |
95 |
125 |
143 |
166 |
198 |
230 |
303 |
355 |
404 |
515 |
624 |
|
|
600/1000V - TWO CORE
STRANDED COPPER CONDUCTOR PVC INSULATED
PVC SHEATHED CABLES (Cu/PVC/PVC)
AND SINGLE STEEL WIRE ARMOURED
PVC SHEATHED CABLES (Cu/PVC/SWA/PVC)
|
|
NOMINAL AREA OF CONDUCTOR |
THICKNESS OF INSULATION |
UN ARMOURED |
ARMOURED |
APPROXIMATE OVERALL DIAMETER |
APPROXIMATE CABLE WEIGHT |
ARMOUR WIRE DIAMETER |
APPROXIMATE OVERALL DIAMETER |
APPROXIMATE CABLE WEIGHT |
Sq mm |
mm |
mm |
Kg/100m |
mm |
mm |
Kg/100m |
1.5* |
2.5* |
4** |
6** |
10** |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
|
0.6 |
0.7 |
0.8 |
0.8 |
1.0 |
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
|
- |
- |
- |
- |
- |
15.6 |
18.4 |
20.1 |
22.8 |
25.5 |
29.3 |
31.8 |
35.1 |
39.1 |
43.9 |
48.7 |
54.2 |
|
- |
- |
- |
- |
- |
47 |
69 |
95 |
126 |
170 |
231 |
288 |
352 |
439 |
576 |
716 |
904 |
|
0.9 |
0.9 |
0.9 |
0.9 |
1.25 |
1.25 |
1.6 |
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.0 |
2.5 |
2.5 |
2.5 |
2.5 |
|
11.7 |
13.1 |
15.1 |
16.5 |
20.1 |
18.9 |
23 |
24.9 |
27.8 |
30.4 |
35.5 |
38.0 |
41.3 |
46.4 |
51.2 |
56.4 |
61.9 |
|
28 |
35 |
46 |
55 |
88 |
84 |
128 |
161 |
201 |
252 |
352 |
420 |
496 |
639 |
802 |
971 |
1185 |
|
|
*CIRCULAR SOLID CONDUCTOR
**CIRCULAR STRANDED CONDUCTORS. CONDUCTORS OF 16 Sq mm AND ABOVE ARE SHAPED STRANDED.
|
600/1 OOOV - TWO CORE
STRANDED ALUMINIUM CONDUCTOR PVC INSULATED
PVC SHEATHED CABLES (AL/PVC/PVC)
AND SINGLE STEEL WIRE ARMOURED
PVC SHEATHED CABLES (AL/PVC/SWA/PVC)
|
NOMINAL AREA OF CONDUCTOR |
THICKNESS OF INSULATION |
UN ARMOURED |
ARMOURED |
APPROXIMATE OVERALL DIAMETER |
APPROXIMATE CABLE WEIGHT |
ARMOUR WIRE DIAMETER |
APPROXIMATE OVERALL DIAMETER |
APPROXIMATE CABLE WEIGHT |
Sq mm |
mm |
mm |
Kg/100m |
mm |
mm |
Kg/100m |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
|
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
|
15.6 |
18.4 |
20.1 |
22.8 |
25.5 |
29.3 |
31.8 |
35.1 |
39.1 |
43.9 |
48.7 |
54.2 |
|
23 |
38 |
53 |
69 |
87 |
116 |
137 |
165 |
206 |
270 |
332 |
413 |
|
1.25 |
1.6 |
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.0 |
2.5 |
2.5 |
2.5 |
2.5 |
|
18.9 |
23.0 |
24.9 |
27.8 |
30.4 |
35.5 |
38.0 |
41.3 |
46.4 |
51.2 |
56.4 |
61.9 |
|
65 |
98 |
119 |
144 |
170 |
238 |
271 |
311 |
406 |
496 |
587 |
694 |
|
|
CONDUCTORS ARE SHAPED STRANDED
|
600/1 OOOV - THREE CORE
STRANDED COPPER CONDUCTOR PVC INSULATED PVC SHEATHED CABLES (Cu/PVC/PVC)
AND SINGLE STEEL WIRE ARMOURED
PVC SHEATHED CABLES (Cu/PVC/SWA/PVC)
|
|
NOMINAL AREA OF CONDUCTOR |
THICKNESS OF INSULATION |
UN ARMOURED |
ARMOURED |
APPROXIMATE OVERALL DIAMETER |
APPROXIMATE CABLE WEIGHT |
ARMOUR WIRE DIAMETER |
APPROXIMATE OVERALL DIAMETER |
APPROXIMATE CABLE WEIGHT |
Sq mm |
mm |
mm |
Kg/100m |
mm |
mm |
Kg/100m |
1.5* |
2.5* |
4** |
6** |
10** |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
|
0.6 |
0.7 |
0.8 |
0.8 |
1.0 |
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2..4 |
2.6 |
|
- |
- |
- |
- |
- |
17.2 |
20.4 |
22.4 |
25.5 |
28.7 |
33.3 |
36.3 |
40.0 |
44.6 |
50.1 |
55.6 |
62.0 |
|
- |
- |
- |
- |
- |
67 |
100 |
130 |
172 |
236 |
333 |
410 |
502 |
626 |
815 |
1014 |
1286 |
|
0.9 |
0.9 |
0.9 |
1.25 |
1.25 |
1.25 |
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.0 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
|
12.3 |
13.6 |
15.8 |
18.0 |
21.2 |
20.6 |
25.0 |
27.3 |
30.5 |
35.0 |
39.3 |
42.2 |
47.5 |
51.9 |
57.8 |
63.2 |
69.6 |
|
31 |
39 |
52 |
73 |
101 |
108 |
167 |
205 |
258 |
359 |
471 |
559 |
711 |
854 |
1079 |
1304 |
1602 |
|
|
*CIRCULAR SOLID CONDUCTOR
**CIRCULAR STRANDED CONDUCTORS. CONDUCTORS OF 16 Sq mm AND ABOVE ARE
SHAPED STRANDED.
|
600/1000V - TWO CORE
STRANDED ALUMINIUM CONDUCTOR PVC INSULATED
PVC SHEATHED CABLES (AL/PVC/PVC)
AND SINGLE STEEL WIRE ARMOURED
PVC SHEATHED CABLES (AL/PVC/SWA/PVC)
|
NOMINAL
AREA
OFCONDUCTOR |
THICKNESS
OF
INSULATION |
UN ARMOURED |
ARMOURED |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
ARMOUR
WIRE
DIAMETER |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
Sq mm |
mm |
mm |
Kg/ 100m |
mm |
mm |
Kg/100m |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
|
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
|
17.2 |
20.4 |
22.4 |
25.5 |
28.7 |
33.3 |
36.3 |
40.0 |
44.6 |
50.1 |
55.6 |
|
38 |
54 |
66 |
90 |
112 |
160 |
182 |
235 |
290 |
344 |
460 |
|
1.25 |
1.6 |
1.6 |
1.6 |
2.0 |
.2.0 |
2.0 |
2.5 |
2.5 |
2.5 |
2.5 |
|
20.6 |
25.0 |
27.3 |
30.5 |
35.0 |
39.3 |
42.2 |
47.5 |
51.9 |
57.8 |
63.2 |
|
79 |
121 |
142 |
176 |
236 |
299 |
342 |
446 |
520 |
640 |
752 |
|
|
CONDUCTORS ARE SHAPED STRANDED
|
600/1000V - FOUR CORE
STRANDED COPPER CONDUCTOR PVC INSULATED
PVC SHEATHED CABLES (Cu/PVC/PVC)
AND SINGLE STEEL WIRE ARMOURED
PVC SHEATHED CABLES (Cu/PVC/SWA/PVC)
|
|
NOMINAL
AREA OF
CONDUCTOR |
THICKNESS
OF INSULATION |
UN ARMOURED |
ARMOURED |
APPROXIMATE
OVERALL DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
ARMOUR
WIRE
DIAMETER |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
Sq mm |
mm |
mm |
Kg/100m |
mm |
mm |
Kg/100m |
1.5* |
2.5* |
4** |
6** |
10** |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
|
0.6 |
0.7 |
0.8 |
0.8 |
1.0 |
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
|
- |
- |
- |
- |
- |
19.3 |
22.9 |
25.4 |
29.2 |
33.0 |
38.3 |
41.8 |
46.3 |
51.3 |
58.0 |
64.6 |
72.0 |
|
- |
- |
- |
- |
- |
86 |
129 |
169 |
225 |
310 |
436 |
538 |
663 |
825 |
1073 |
1338 |
1693 |
|
0.9 |
0.9 |
1.25 |
1.25 |
1.25 |
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.0 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
3.15 |
|
13.3 |
14.5 |
17.8 |
19.2 |
22.8 |
23.9 |
27.8 |
30.5 |
35.4 |
39.2 |
44.3 |
49.3 |
53.6 |
59.0 |
65.7 |
72.0 |
81.3 |
|
35 |
44 |
71 |
85 |
120 |
149 |
205 |
253 |
348 |
447 |
590 |
754 |
987 |
1089 |
1369 |
1661 |
2148 |
|
|
*CIRCULAR SOLID CONDUCTOR
**CIRCULAR STRANDED CONDUCTORS. CONDUCTORS OF 16 Sq mm AND ABOVE ARE
SHAPED STRANDED.
|
600/1000V - FOUR CORE
STRANDED ALUMINIUM CONDUCTOR PVC INSULATED
PVC SHEATHED CABLES (ALlPVC/PVC)
AND SINGLE (STEEL) WIRE ARMOURED
PVC SHEATHED CABLES (ALlPVC/SWA/PVC)
|
NOMINAL AREA OF CONDUCTOR |
THICKNESS OF INSULATION |
UN ARMOURED |
ARMOURED |
APPROXIMATE OVERALL DIAMETER |
APPROXIMATE CABLE WEIGHT |
ARMOUR WIRE DIAMETER |
APPROXIMATE OVERALL DIAMETER |
APPROXIMATE CABLE WEIGHT |
Sq mm |
mm |
mm |
Kg/100m |
mm |
mm |
Kg/100m |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
|
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
|
19.3 |
22.9 |
25.4 |
29.2 |
33.0 |
38.3 |
41.8 |
46.3 |
51.3 |
58.0 |
64.6 |
|
48 |
64 |
84 |
113 |
145 |
206 |
248 |
306 |
378 |
485 |
599 |
|
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.0 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
|
23.9 |
27.9 |
30.5 |
35.4 |
39.2 |
44.3 |
49.3 |
53.6 |
59.0 |
65.7 |
72.0 |
|
111 |
144 |
169 |
240 |
283 |
361 |
465 |
542 |
644 |
783 |
924 |
|
|
CONDUCTORS ARE SHAPED STRANDED
|
600/1000V - ( 3 CORE)
STRANDED COPPER CONDUCTOR PVC INSULATED CONDUCTOR ( 3 CORE)
PVC SHEATHED CABLES (Cu/PVC/PVC)
AND SINGLE STEEL WIRE ARMOURED
PVC SHEATHED CABLES (Cu/PVC/SWA/PVC)
|
|
NOMINAL
AREA OF
CONDUCTOR
|
NOMINAL
AREA
OF
NEUTRAL
CONDUCTOR |
UN ARMOURED |
|
ARMOURED |
THICKNESS
OF
INSULATION |
APPROXIMATE
OVER ALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
ARMOUR
WIRE
DIAMETER |
APPROXIMATE
OVER ALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
Sq mm |
Sq mm |
mm |
mm |
Kg/100m |
mm |
mm |
Kg/100m |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
300 |
400 |
|
16 |
16 |
25 |
35 |
50 |
70 |
70 |
95 |
120 |
150 |
185 |
185 |
|
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.4 |
2.6 |
|
22.9 |
24.7 |
28.3 |
32.0 |
37.5 |
41.4 |
44.7 |
49.9 |
56.0 |
62.2 |
64.2 |
69.6 |
|
126 |
159 |
212 |
289 |
392 |
489 |
590 |
740 |
959 |
1191 |
1219 |
1507 |
|
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
3.15 |
|
27.8 |
29.5 |
33.1 |
38.0 |
43.7 |
49.0 |
52.0 |
57.2 |
63.7 |
69.8 |
71.8 |
78.6 |
|
202 |
243 |
305 |
422 |
456 |
699 |
818 |
991 |
1247 |
1508 |
1536 |
1947 |
|
|
ALL PHASE CONDUCTORS ARE SHAPED STRANDED
ALL NETURAL CONDUCTORS ARE CIRCULAR STRANDED
|
1900/3300V- SINGLE CORE
STRANDED COPPER CONDUCTOR PVC INSULATED
PVC SHEATHED CABLE (Cu/PVC/PVC)
AND SINGLE ALUMINIUM WIRE ARMOURED
PVC SHEATHED CABLE (Cu/PVC/AWA/PVC)
|
NOMINAL
AREA OF
CONDUCTOR |
THICKNESS
OF INSULATION |
UN ARMOURED |
|
ARMOURED |
|
ARMOUR
WIRE
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
APPROXIMATE
OVERALL
DIAMETER |
Sq mm |
mm |
mm |
Kg/100m |
mm |
mm |
Kg/100m |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
|
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.4 |
2.6 |
2.8 |
2.8 |
2.8 |
3.0 |
|
16.8 |
18.8 |
20.7 |
22.6 |
24.1 |
26.2 |
29.0 |
32.1 |
35.8 |
39.6 |
43.8 |
48.3 |
53.7 |
|
66 |
89 |
116 |
143 |
171 |
209 |
267 |
332 |
419 |
523 |
663 |
833 |
1044 |
|
1.25 |
1.25 |
1.6 |
1.6 |
1.6 |
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.0 |
2.5 |
2.5 |
|
21.0 |
22.8 |
26.0 |
27.6 |
29.4 |
31.3 |
34.1 |
37.0 |
42.0 |
45.6 |
49.7 |
55.8 |
61 |
|
87 |
111 |
149 |
177 |
207 |
247 |
309 |
377 |
483 |
592 |
742 |
850 |
1176 |
|
|
CONDUCTORS ARE SHAPED STRANDED
|
1900/3300V - SINGLE CORE
STRANDED ALUMINIUM CONDUCTOR PVC INSULATED PVC SHEATHED CABLES (ALlPVC/PVC)
AND SINGLE ALUMINIUM WIRE ARMOURED
PVC SHEATHED CABLES (ALlPVC/AWNPVC)
|
NOMINAL
AREA OF
CONDUCTOR |
THICKNESS
OF
INSULATION |
UN ARMOURED |
ARMOURED |
APPROXIMATE
OVERALL DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
ARMOUR
WIRE
DIAMETER |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
Sq mm |
mm |
mm |
Kg/100m |
mm |
mm |
Kg/100m |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
|
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.4 |
|
16.8 |
18.8 |
20.7 |
22.6 |
24.1 |
26.2 |
29.0 |
32.1 |
|
34 |
44 |
54 |
63 |
74 |
88 |
109 |
134 |
|
1.25 |
1.25 |
1.6 |
1.6 |
1.6 |
1.6 |
1.6 |
1.6 |
|
21 |
22.8 |
26 |
27.6 |
29.4 |
31.3 |
34.1 |
37 |
|
77 |
90 |
122 |
136 |
151 |
170 |
198 |
230 |
|
|
CONDUCTORS ARE CIRCULAR STRANDED
|
1900/3300V - THREE CORE
STRANDED COPPER CONDUCTOR PVC INSULATED
SINGLE STEEL WIRE ARMOURED
PVC SHEATHED CABLES (Cu/PVC/SWNPVC)
|
NOMINAL AREA
OF CONDUCTOR |
THICKNESS OF
INSULATION |
ARMOUR
WIRE
DIAMETER |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
Sqmm |
mm |
mm |
mm |
Kg/100 m |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
|
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.4 |
2.6 |
|
1.6 |
1.6 |
1.6 |
2.0 |
2.0 |
2.0 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
|
27.6 |
29.9 |
32.1 |
35.6 |
38.9 |
42.3 |
46.6 |
49.4 |
52.8 |
57.8 |
63.2 |
69.6 |
|
175 |
215 |
257 |
333 |
414 |
511 |
645 |
743 |
873 |
1083 |
1309 |
1609 |
|
|
CONDUCTORS ARE CIRCULAR STRANDED
|
1900/3300V - THREE CORE
ALUMINIUM STRANDED CONDUCTOR PVC INSULATED
SINGLE STEEL WIRE ARMOURED
PVC SHEATHED CABLES (Cu/PVC/SWNPVC
|
NOMINALAREA
OF CONUCTOR |
THICKNESS OF
INSULATION |
ARMOUR WIRE
DIAMETER |
APPROXIMATE
OVERALL
DIAMETER |
APPROXIMATE
CABLE
WEIGHT |
Sq mm |
mm |
mm |
mm |
Kg/100 m |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
|
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.2 |
2.4 |
|
1.6 |
1.6 |
1.6 |
2 |
2 |
2 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
|
27.6 |
29.9 |
32.1 |
35.6 |
38.9 |
42.3 |
46.6 |
49.4 |
52.8 |
57.8 |
63.2 |
|
134 |
154 |
177 |
228 |
265 |
309 |
390 |
434 |
490 |
586 |
688 |
|
|
CONDUCTORS ARE SHAPED STRANDED
|
CURRENT RATINGS FOR CABLES INSTALLED IN AIR
600/1 OOOV - SINGLE, TWIN, THREE AND FOUR CORE
STRANDED COPPER CONDUCTORS PVC INSULATED
SINGLE WIRE ARMOURED PVC SHEATHED CABLES (Cu/PVC/SWAlPVC)
|
NOMINAL
AREA OF
CONDUCTOR |
SINGLE CORE*
TWO CABLES SPACED+ |
|
TWO CORE |
THREE & FOUR CORE |
THREE CABLES
TREFOIL TOUCHING |
|
|
|
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
Sqmm |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
1.5* |
2.5* |
4 |
6 |
10 |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
|
- |
- |
- |
- |
- |
- |
- |
- |
205 |
255 |
310 |
360 |
405 |
460 |
530 |
600 |
660 |
730 |
820 |
880 |
960 |
|
- |
- |
- |
- |
- |
- |
- |
- |
0.96 |
0.69 |
0.54 |
0.46 |
0.41 |
0.36 |
0.36 |
0.33 |
0.30 |
0.28 |
0.26 |
0.24 |
0.22 |
|
- |
- |
- |
- |
- |
- |
- |
- |
180 |
230 |
280 |
325 |
370 |
425 |
500 |
570 |
640 |
720 |
810 |
870 |
940 |
|
- |
- |
- |
- |
- |
- |
- |
- |
0.81 |
0.57 |
0.43 |
0.36 |
0.31 |
0.26 |
0.23 |
0.2 |
0.19 |
0.18 |
0.16 |
0.16 |
0.15 |
|
21 |
30 |
39 |
50 |
69 |
90 |
120 |
150 |
175 |
220 |
270 |
310 |
355 |
410 |
485 |
550 |
620 |
- |
- |
- |
- |
|
28 |
17 |
11 |
7.4 |
4.4 |
2.8 |
1.7 |
1.3 |
0.94 |
0.66 |
0.49 |
0.40 |
0.34 |
0.29 |
0.24 |
0.21 |
0.19 |
- |
- |
- |
- |
|
19 |
25 |
33 |
43 |
59 |
77 |
100 |
125 |
155 |
190 |
235 |
270 |
310 |
355 |
420 |
475 |
550 |
- |
- |
- |
- |
|
25 |
15 |
19.6 |
6.4 |
3.8 |
2.4 |
1.5 |
1.1 |
0.82 |
0.57 |
0.42 |
0.35 |
0.29 |
0.25 |
0.21 |
0.18 |
0.17 |
- |
- |
- |
- |
|
|
* ALUMINIUM ARMOURED
** CIRCULAR SOLID CONDUCTOR
DISTANCE BETWEEN CABLE CENTRES: UPTO & INCLUDING 185 Sq mm SHALL BE TWICE THE CABLE DIAMETER
and 240 Sq mm AND ABOVE - 90 mm
|
CURRENT RATINGS FOR CABLES INSULATED IN AIR
600/1000V - SINGLE, TWIN, THREE AND FOUR CORE
STRANDED ALUMINIUM CONDUCTORS PVC INSULATED
SINGLE WIRE ARMOURED PVC SHEATHED CABLES (ALlPVC/SWA/PVC)
|
|
NOMINAL
AREA OF
CONDUCTOR |
SINGLE CORE*
TWO CABLES SPACED+ |
|
TWO CORE |
THREE & FOUR CORE |
THREE CABLES
TREFOIL TOUCHING |
|
|
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
Sqmm |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
380 |
480 |
600 |
740 |
960 |
1200 |
|
- |
- |
- |
155 |
190 |
235 |
270 |
305 |
350 |
420 |
475 |
520 |
590 |
650 |
710 |
800 |
880 |
|
- |
- |
- |
1.5 |
1.1 |
0.81 |
0.67 |
0.57 |
0.59 |
0.44 |
0.39 |
0.35 |
0.32 |
0.30 |
0.28 |
0.25 |
0.23 |
|
- |
- |
- |
135 |
170 |
210 |
245 |
280 |
320 |
375 |
430 |
495 |
560 |
630 |
710 |
790 |
870 |
|
- |
- |
- |
1.3 |
0.92 |
0.68 |
0.55 |
0.46 |
0.38 |
0.31 |
0.26 |
0.24 |
0.21 |
0.19 |
0.18 |
0.17 |
0.16 |
|
68 |
90 |
110 |
130 |
165 |
195 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
4.5 |
2.9 |
2.1 |
1.5 |
1.1 |
0.79 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
58 |
78 |
93 |
110 |
145 |
175 |
205 |
235 |
270 |
320 |
370 |
- |
- |
- |
- |
- |
- |
|
3.9 |
2.5 |
1.8 |
1.3 |
0.93 |
0.68 |
0.54 |
0.45 |
0.37 |
0.29 |
0.25 |
- |
- |
- |
- |
- |
- |
|
|
* ALUMINIUM WIRE ARMOURED
* DISTANCE BETWEEN CABLE CENTRES: UPTO & INCLUDING 185 mm2 - SHALL BE TWICE THE CABLE DIAMETER
240 mm2 & ABOVE - 90 MM.
|
BASIC ASSUMPTIONS AND CONDITIONS OF INSTALLATION:
|
AMBIENT AIR TEMPERATURE.......................................................... 30 ° C
MAXIMUM CONDUCTOR OPERATING
TEMPERATURE AT RATED CURRENT...............................................70 ° C
METHOD OF INSTALLATION:
Cables shall only be continuously operated at their full rating if the minimum current at which
circuit protection is designed to operate does not exceed 1.5 times the values tabulated.
EFFECT OF GROUPING OF CABLES:
Single core cables installed in the manner indicated in the tabes. Twin and multicore installed in
"defined conditions" in accordance with the lEE Wiring Regulations.
No reduction in rating is necessary providing that:
1. The horizontal clearance between circuit is
(A) Not less than six times the overall diameter of an individual cable
(b) Not less than the overall width of an individual circuit, except that the horizontal clearance need not in any case exceed 150 mm.
2.The vertical clearance between circuits is not less than 150 mm.
3. If the number of circuits exceeds 4, they are installed in a horizontal plane.
|
RATING FACTORS FOR OTHER AMBIENT AIR TEMPERATURES
AMBIENT AIR TEMPERATURE °C |
23 |
35 |
40 |
45 |
50 |
RATING FACTOR |
1.08 |
0.94 |
0.86 |
0.77 |
0.70 |
|
For the other conditions of installation, reference should be made to ERA
|
|
CURRENT RATINGS FOR CABLES INSTALLED IN AIR
600/1000V - SINGLE, TWIN, THREE AND FOUR CORE
STRANDED COPPER CONDUCTORS PVC INSULATED
PVC SHEATHED CABL_S (CU/PVC/PVC
|
NOMINAL
AREA OF
CONDUCTOR |
SINGLE CORE |
TWO CORE |
THREE & FOUR CORE |
TWO CABLES
SPACED* |
THREE CABLES
TREFOIL TOUCHING |
LAID*
FLAT SPACED |
|
|
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
Sqmm |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
16* |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
730 |
800 |
1000 |
|
- |
- |
- |
190 |
245 |
300 |
355 |
410 |
475 |
590 |
680 |
790 |
990 |
1050 |
1200 |
1330 |
|
- |
- |
- |
0.95 |
0.68 |
0.52 |
0.44 |
0.39 |
0.35 |
0.36 |
0.33 |
0.30 |
0.28 |
0.26 |
0.24 |
0.22 |
|
- |
- |
- |
170 |
220 |
270 |
310 |
360 |
420 |
495 |
580 |
660 |
760 |
770 |
990 |
1100 |
|
- |
- |
- |
0.80 |
0.57 |
0.42 |
0.35 |
0.29 |
0.25 |
0.21 |
0.19 |
0.17 |
0.16 |
0.15 |
0.15 |
0.14 |
|
- |
- |
- |
185 |
235 |
300 |
345 |
395 |
460 |
590 |
580 |
780 |
890 |
1030 |
1170 |
1290 |
|
- |
- |
- |
0.83 |
0.60 |
0.47 |
0.40 |
0.35 |
0.33 |
0.32 |
0.31 |
0.28 |
0.27 |
0.25 |
0.23 |
0.22 |
|
86 |
115 |
145 |
170 |
220 |
265 |
305 |
350 |
400 |
475 |
550 |
630 |
- |
- |
- |
- |
|
2.8 |
1.7 |
1.3 |
0.94 |
0.66 |
0.49 |
0.40 |
0.34 |
0.29 |
0.24 |
0.21 |
0.19 |
- |
- |
- |
- |
|
73 |
98 |
120 |
150 |
185 |
230 |
265 |
300 |
350 |
415 |
475 |
550 |
- |
- |
- |
- |
|
2.4 |
1.5 |
1.1 |
0.82 |
0.57 |
0.42 |
0.35 |
0.29 |
0.25 |
0.21 |
0.18 |
0.17 |
- |
- |
- |
- |
|
|
* DISTANCE BETWEEN CABLE CENTRES: UPTO AND INCLUDING 185 Sq mm SHALL BE TWICE THE CABLE DIAMETER 240 Sq mm AND ABOVE - 90 mm.
|
CURRENT RATINGS FOR CABLES INSTALLED IN AIR
600/1000V - SINGLE, TWIN, THREE AND FOUR CORE
STRANDED ALUMINIUM CONDUCTORS PVC INSULATED
PVC SHEATHED CABLES (ALlPVC/PVC)
|
NOMINAL
AREA OF
CONDUCTOR |
SINGLE CORE |
TWO CORE |
THREE & FOUR CORE |
TWO CABLES
SPACED* |
THREE CABLES
TREFOIL TOUCHING |
LAID*
FLAT SPACED |
|
|
CURRENT
RATING |
APPROXIMATE
VOLT DROP PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP PER AMPERE
PER METREE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP PER AMPERE
PER METRE |
Sqmm |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
380 |
480 |
600 |
740 |
960 |
1200 |
|
- |
- |
- |
145 |
180 |
225 |
260 |
300 |
350 |
440 |
500 |
580 |
670 |
760 |
870 |
1020 |
1150 |
|
- |
- |
- |
1.5 |
1.1 |
0.8 |
0.65 |
0.55 |
0.46 |
0.43 |
0.38 |
0.35 |
0.32 |
0.29 |
0.27 |
0.25 |
0.17 |
|
- |
- |
- |
125 |
165 |
200 |
235 |
265 |
310 |
370 |
430 |
495 |
580 |
650 |
750 |
880 |
1000 |
|
- |
- |
- |
1.3 |
0.9 |
0.67 |
0.54 |
0.45 |
0.37 |
0.3 |
0.25 |
0.23 |
0.2 |
0.18 |
0.17 |
0.16 |
0.15 |
|
- |
- |
- |
140 |
175 |
220 |
255 |
295 |
340 |
440 |
500 |
580 |
660 |
750 |
860 |
1000 |
1130 |
|
- |
- |
- |
1.3 |
0.95 |
0.72 |
0.6 |
0.51 |
0.45 |
0.43 |
0.39 |
0.37 |
0.3 |
0.28 |
0.26 |
0.24 |
0.23 |
|
65 |
86 |
105 |
125 |
160 |
195 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
4.5 |
2.9 |
2.1 |
1.5 |
1.1 |
0.79 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
56 |
74 |
91 |
110 |
140 |
170 |
200 |
230 |
260 |
310 |
360 |
- |
- |
- |
- |
- |
- |
|
3.9 |
2.5 |
1.8 |
1.3 |
0.93 |
0.68 |
0.54 |
0.45 |
0.37 |
0.29 |
0.25 |
- |
- |
- |
- |
- |
- |
|
|
* DISTANCE BETWEEN CABLE CENTRES: UPTO AND INCLUDING 185 Sq mm SHALL BE TWICE THE
CABLE DIAMETER 240 Sq mm AND ABOVE - 90 mm.
|
BASIC ASSUMPTIONS AND CONDITIONS OF INSTALLATION:
|
RATING FACTORS FOR OTHER AMBIENT AIR TEMPERATURES
AMBIENT AIR TEMPERATURE °C |
23 |
35 |
40 |
45 |
50 |
RATING FACTOR |
1.08 |
0.94 |
0.86 |
0.77 |
0.70 |
|
For the other conditions of installation, reference should be made to ERA
|
CURRENT RATINGS FOR CABLES LAID DIRECT IN GROUND
600/1000V - SINGLE, TWIN, THREE AND FOUR CORES
STRANDED COPPER CONDUCTOR PVC INSULATED
SINGLE WIRE ARMOURED PVC SHEATHED CABLES (Cu/PVC/SWA/PVC)
|
|
NOMINAL
AREA OF
CONUCTOR |
SINGLE CORE** |
|
TWO CORE |
|
THREE & FOUR CORE |
TWO CABLES TOUCHING |
THREE CABLES
TREFOIL TOUCHING |
|
|
|
|
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
CURRENT
RATING |
APPROXIMATE
VOLT DROP
PER AMPERE
PER METRE |
Sq mm2 |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
AMPERE |
mV |
1.5* |
2.5* |
4 |
6 |
10 |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
|
- |
- |
- |
- |
- |
- |
- |
- |
235 |
290 |
345 |
390 |
440 |
490 |
570 |
630 |
700 |
770 |
850 |
890 |
940 |
|
- |
- |
- |
- |
- |
- |
- |
- |
0.93 |
0.66 |
0.5 |
0.41 |
0.36 |
0.3 |
0.26 |
0.23 |
0.22 |
0.2 |
0.19 |
0.18 |
0.18 |
|
- |
- |
- |
- |
- |
- |
- |
- |
200 |
245 |
295 |
335 |
370 |
415 |
480 |
530 |
590 |
640 |
710 |
740 |
780 |
|
- |
- |
- |
- |
- |
- |
- |
- |
0.81 |
0.57 |
0.43 |
0.36 |
0.31 |
0.26 |
0.23 |
0.2 |
0.19 |
0.18 |
0.16 |
0.16 |
0.15 |
|
30 |
40 |
53 |
66 |
88 |
115 |
150 |
185 |
215 |
270 |
320 |
365 |
410 |
465 |
540 |
600 |
670 |
- |
- |
- |
- |
|
28 |
17 |
11 |
7.4 |
4.4 |
2.8 |
1.7 |
1.3 |
0.94 |
0.66 |
0.49 |
0.4 |
0.34 |
0.29 |
0.24 |
0.21 |
0.19 |
- |
- |
- |
- |
|
26 |
34 |
45 |
57 |
75 |
98 |
130 |
155 |
185 |
225 |
270 |
310 |
345 |
390 |
455 |
510 |
570 |
- |
- |
- |
- |
|
25 |
15 |
9.6 |
6.4 |
3.8 |
2.4 |
1.5 |
1.1 |
0.82 |
0.57 |
0.42 |
0.35 |
0.29 |
0.25 |
0.21 |
0.18 |
0.17 |
- |
- |
- |
- |
|
|
*CIRCULAR SOLID CONDUCTORS
** ALUMINIUM WIRE ARMOURED
|