750V 60°C PVC INSULATED AND SHEATHED FLEXIBLE CABLE.
NUMBER OF CORES : Up to 4 cores.
CONDUCTOR  : Flexible annealed copper wires.
Sizes 0.5 mm2 up to 95 mm2for single core.
0.5 mm2 up to 35 mm2 for multi core.
INSULATION : PVC
  Colour: Single core 
2 core 
3 core 
4 core 
- Black
- Light grey, Black
- Light grey, Black, Red.
- Light grey, Black, Red, Blue.
SHEATH : PVC.
  :Colour: Black
CLASSIFICATION : Maximum conductor temperature 60°C
CIRCUIT G VOLTAGE : Circuit voltage not exceeding 750 volts.


600/1000 Volts
Flexible anealed Copper wires
0.5 mm2 up to 95 mm2 for Single core
0.5 mm2 up to 35 mm2 for Multi Core.
Circuit Voltage not exceeding 750 Volts

Number
of
core
Nominal
cross
sectional
area
Number
and
diameter
of wire
Mean
value of
insulation
thickness
Mean
value of
sheath
thickness
Maximum
overall
diameter
Minimum
insulation
resistance
at 60 C
Maximum
continuous
current
rating
in free air
Cable
weight
(approx.)
  (mm2) (No/mm) (mm) (mm) (mm) (M Ω-km) (Ampere) (Kg/Km)
1
0.5
0.75
1
1.5
2.5
4
6
10
16
25
35
50
70
95
16/0.20
24/0.20
32/0.20
30/0.25
50/0.25
56/0.30
84/0.30
80/0.40
126/0.40
196/0.40
270/0.40
396/0.40
360/0.50
475/0.50
0.8
. 0.8
0.8
0.8
0.8
0.9
0.9
1.1
1.1
1.3
1.3
1.5
1.5
1.7
1
1
1.2
1.2
1.2
1.4
1.4
1.8
1.8
2.2
2.2
2.6
2.6
3
5.2
5.4
5.9
6.2
6.7
7.8
8.4
10.6
11.6
14.2
15.6
18.3
20.2
23
0.032
0.028
0.025
0.022
0.018
0.017
0.014
0.013
0.011
0.011
0.009
0.009
0.008
0.008
9
11
13
16
22
30
39
57
75
99
120
150
190
210
29
33
41
48
60
90
110
210
270
410
540
750
980
1,300
2
0.5
0.75
1
1.5
2.5
4
6
10
16
25
35
16/0.20
24/0.20
32/0.20
30/0.25
50/0.25
56/0.30
84/0.30
85/0.40
126/0.40
196/0.40
276/0.40
0.8
0.8
0.8
0.8
0.8
0.9
0.9
1.1
1.1
1.3
1.3
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2
2.4
2.6
8.2
8.6
9
9.9
10.8
12.7
14.2
17.3
20.3
24.2
27
0.032
0.028
0.025
0.022
0.018
0.017
0.014
0.013
0.011
0.011
0.009
8
10
12
15
21
28
36
52
69
90
110
80
90
95
120
160
230
290
510
710
1.03
1.38
3
0.5
0.75
1
1.5
2.5
4
6
10
16
25
35
16/0.20
24/0.20
32/0.20
30/0.25
50/0.25
56/0.30
84/0.30
80/0.40
126/0.40
196/0.40
276/0.40
0.8
0.8
0.8
0.8
0.8
0.9
0.9
1.1
1.1
1.3
1.3
1.2
1.2
1.4
1.4
1.4
1.6
1.8
2.2
2.4
2.6
2.8
8.6
9
9.8
10.4
11.4
13.6
15.3
18.7
22
26
29
0.032
0.028
0.025
0.022
0.018
0.017
0.014
0.013
0.011
0.011
0.009
7
9
10
13
18
24
31
45
60
78
96
90
100
120
140
190
280
370
650
900
1,320
1,770
4
0.5
0.75
1
1.5
2.5
4
6
10
16
25
35
16/0.20
24/0.20
32/0.20
30/0.25
50/0.25
56/0.30
84/0.30
80/0.40
126/0.40
196/0.40
276/0.40
0.8
0.8
0.8
0.8
0.8
0.9
0.9
1.1
1.1
1.3
1.3
1.4
1.4
1.6
1.6
1.6
1.8
2
2.2
2.6
2.8
3.1
9.6
10.2
11
11.6
12.8
15.2
17
20.8
24.3
28.8
32.3
0.032
0.028
0.025
0.022
0.018
0.017
0.014
0.013
0.011
0.011
0.009
6
8
9
12
16
22
29
41
54
71
88
110
130
150
180
240
350
480
820
1.5
1.68
2.29


Flexible Wires and Cables
250V 60°C PVC INSULATED AND SHEATHED FLAT TYPE, FLEXIBLE CONDUCTOR.
NUMBER OF CORES : 2 cores.
CONDUCTOR  : Flexible annealed copper wires, size 0.5 mm2 up to 35 mm2 PVC
INSULATION : PVC
  Colour: Lightgrey,black PVC 
SHEATH : PVC.
  :Colour: BlackBlack or white
CLASSIFICATION : Maximum conductor temperature 60°C
  : Circuit voltage not exceeding 250 volts.

Number
of
core
Nominal
cross
sectional
area
Number
and
diameter
of wire
Mean
value of
insulation
thickness
Mean
value of
sheath
thickness
Avera overall
diameter

(mm)
Minimum
insulation
resistance
at 60 C
Maximum
continuous
current
rating infree air
Cable
weight
(approx.)
  (mm2) (No/mm) (mm) (mm)
Lower limit Upper limit
(MΩ-Km) (Ampere) (Kg/Km)
2
0.5
0.5
1
1.5
2.5
4
6
10
16
25
35
28/0.15
16/0.20
32/0.20
30/0.25
50/0.25
56/0.30
84/0.30
80/0.40
126/0.40
196/0.40
276/0.40
0.6
0.6
0.6
0.6
0.7
0.8
0.8
0.9
1
1,2
1.2
0.9
0.9
0.9
1.2
1.2
1.2
1.2
1.2
1.2
1.4
1.4
3.8 x 5.8 4.6 x 6.6
3.8 x 5.8 4.6 x 6.6
4.7 x 6.5 4.9 x 7.2
5.0 x 7.6 5.7 x 8.3
5.6 x  8.8 6.3 x 9.5
6.2 x 10.1 7.0 x 10.9
7.1 x 11.8 7.9 x 12.6
8.2 x 14.1 9.3 x 15.1
9.5 x 16.6 10.5 x 17.6
11,6 x 20.4 12,9 x21.7
12.8 x 22.9 14.1 x24.2
0.026
0.026
0.021
0.018
0.016
0.015
0.013
0.011
0.01
0.009
0.008
6
6
9
12
17
22
29
41
55
73
91
38
38
55
75
110
150
200
330
460
700
940


Flexible Wires and Cables
250V 60°C PVC INSULATED AND SHEATHED FLAT TYPE, FLEXIBLE CONDUCTOR.
NUMBER OF CORES : 2
CONDUCTOR  : Flexible annealed copper wires, size 0.5 mm2 up to 2.5 mm2
INSULATION : PVC
  Colour: Any colour with one different colour tracer on lateral  side of wire, or colour thread at one of conductors
CLASSIFICATION : Maximum conductor temperature 60°C
CIRCUIT VOLTAGE : Circuit voltage not exceeding 250 volts.

Number
of
core
Nominal
cross
sectional
area
Number
and
diameter
of wire
Mean
value of
insulation
thickness
Maximum
overall
diameter
Minimum
insulation
resistance
at 60 C
Maximum
continuous
current
rating
in free air
Cable
weight
(approx.)
  (mm2) (No/mm) (mm) (mm) (mm) (Ampere) (Kg/Km)
2
0.5
0.5
0.75
0.75
1
1.5
2.5
28/0.15
16/0.20
42/0.15
24/0.20
32/0.20
30/0.25
50/0.25
0.8
0.8
0.8
0.8
0.8
0.8
0.8
3.3 x 5.8
3.3 x 5.8
3.5 x 6.2
3.5 x 6.2
3.7 x 6.6
3.9 x 7.1
4.4 x 8.0
0.032
0.032
0.028
0.028
0.025
0.022
0.018
7
7
9
9
11
14
20
22
22
27
28
33
44
65


Flexible Wires and Cables
250V 60°C PVC INSULATED FLEXIBLE CONDUCTOR, SINGLE CORE.
CONDUCTOR  : Flexible annealed copper wires, size 0.5 mm2 up to 2.5 mm2
INSULATION : PVC - Any colour.
CLASSIFICATION : Maximum conductor temperature 60°C
CIRCUIT VOLTAGE : Circuit voltage not exceeding 250 volts.

CURRENT RATINGS
FLEXIBLE CORDS PVC TO BS 6500
Conductor Current
Rating
(Subject to
Volt arop) dc or
1 - phase or
3 - phase
Maximum
premissible weight
supported by
a twin cord
(See reg. B. 132
I.E.E. Regs.)
Nominal cross
sectional
area
Number
and
diameter of wires
mm2
0.5
0.75
1
1.25
1.5
2.5
4
No./mm
16/0.20
24/0.20
32/0.20
40/0.20
30/0.25
50/0.25
56/0.30
amp
3
6
10
13
15
20
25
Kg
2
3
5
5
5
5
5


PVC insulated (non-armoured) cables
CONDUCTOR
SIZE
Nominal Area
mm2
1.0
 
1.5
(1/1.38)
1.5
(7/0.50)
2.5
(1/1.78)
2.5
(7/0.67)
4
 
6
 
10
 
16
 
25
 
35
 
IN TRUNKING OR
CONDUIT
1 or 2 single core
1 twin
3 or 4 single core
1 three or four core
+
+
amps
11.14*
11
9
9
amps
13.17*
13
11
12
amps
13.17*
-
11
-
amps
18.24*
18
16
16
amps
18.24*
-
16
-
amps
24.31*
24
22
22
amps
31.40*
30
28
27
amps
42.55*
40
39
37
amps
56.73*
53
50
47
amps
73.94*
60
66
53
amps
90.115*
74
80
65
ON CABLE TRAY
OR CLIPPED
DIRECT TO
SURFACE
+ 1 or 2 single core
1 twin
3 or 4 single core
1 three or four core
+
 
13
12
12
10
 
16
15
15
13
 
16
-
15
-
 
23
21
26
18
 
23
-
20
-
 
30
27
27
24
 
38
35
34
30
 
51
48
46
41
 
68
64
61
54
 
89
71
80
62
 
109
87
98
72

The above ratings apply where coarse excess current protection is provided and are subject to voltage drop consideration
+ These ratings are for flat cables 1 mm2 to 16mm2 inclusive and circular cables 25mm2 and 35mm2
For ratings of circular cables 1 mm2 to 16mm2 inclusive refer to I.EE Regulations.


VOLTAGE GRADES

PVC or insulated (non-armoured) cables
Approximate voltage drop per ampere per metre
CONDUCTOR
SIZE
Nominal Area
mm2
1.0
 
1.5
(1/1.38)
1.5
(7/0.50)
2.5
(1/1.78)
2.5
(7/0.67)
4
 
6
 
10
 
16
 
25
 
35
 
IN TRUNKING OR
CONDUIT
1 or 2 single core
1 twin
3 or 4 single core
1 three or four core
+
+
mV
40.42*
40
35
35
mV
27.28*
27
23
23
mV
30.32*
-
26
-
mV
16-17*
16
14
14
mV
16.18*
-
14
-
mV
10.11*
10
8.8
8.8
mV
68.72*
6.8
5.9
5.9
mV
4.43*
4.0
3.5
3.5
mV
26.22*
2.6
2.2
2.2
mV
16.17*
1.7
1.4
1.5
mV
12.12*
1.2
1.0
1.0
ON CABLE TRAY
OR CLIPPED
DIRECT TO
SURFACE
+ 1 or 2 single core
1 twin
3 or 4 single core
1 three or four core
+
 
40
40
35
35
 
27
27
23
23
 
30
-
26
-
 
16
16
14
14
 
16
-
14
-
 
10
10
8.8
8.8
 
6.8
6.8
5.9
5.9
 
4.0
4.0
3.5
3.5
 
2.6
2.6
2.2
2.2
 
1.6
1.7
1.4
1.5
 
1.2
1.2
1.0
1.0

+ Voltage drops are for flat cables 1 mm2 to 16mm2 inclusive and circular cables 25mm2 and 35mm2
For volt drop ratings of circular cables 1 mm2 to 16mm2 inclusive refer to I.E.E. Regulations.


VOLTAGE DROP

Cable described as 600/1000 volt are suitable for use on a circuit where the voltage to earth does not exceed 600 volt and between conductors, 1000 volt. Cables, flexible Cables and Flexible Cords described as 450/750 volt. Cables. Flexible Cables and Flexible Cord described as 300/500 volt are suitable for use on a circuit where the voltage to earth does not exceed 300 volt and between conductors, 500 volt, Total volt drop between consumers terminals and any other part of the installation must not exceed 2.5% of the nominal voltage. Refer lEE Regulation & ERA Report.
 
 
 
  Copyright © 2007 Allied Cables. | Website Designed by Salsabil Home   |   Profile   |   Products   |    Clientele   |   Feedback   |   Contacts